Voltage Drop Calculations on the Electrician Exam: The NEC Formula, K Values and Worked Examples

How to calculate voltage drop for the journeyman electrician exam: the single- and three-phase formulas, K = 12.9 and 21.2, Chapter 9 Table 8 circular mils, the 3%/5% recommendation, and worked examples for drop, wire size and maximum length.

Problem this solves

This guide solves the next-step problem for Electrician candidates: it explains what matters, then gives you a direct way to test that knowledge with practice questions instead of guessing what to study next.

TL;DR

To calculate voltage drop on the journeyman electrician exam, use VD = (2 × K × I × L) ÷ CM for single-phase or VD = (1.732 × K × I × L) ÷ CM for three-phase, where K is 12.9 for copper and 21.2 for aluminum, I is the load in amps, L is the one-way length in feet and CM is the conductor area from NEC Chapter 9, Table 8. Divide the drop by the system voltage to get the percent, and compare it with the 3% branch-circuit and 5% total recommendation. To find a wire size, solve the same formula for CM and round up to the next size in Table 8.

Try it now — no account, no download

Practice Electrician questions free

Answer 5 Electrician practice questions with instant explanations before you keep reading.

Electrician · Question 1 of 5

What is the minimum size copper grounding electrode conductor required for a service supplied by 3/0 AWG copper service-entrance conductors?

Pick an answer to see the explanation + an instant AI breakdown.

Why Voltage Drop Is on the Exam

Every conductor has resistance, so some voltage is lost as heat between the panel and the load. Motors run hot, lights dim and electronics reset when the drop gets too large, which is why designers size wire for voltage drop as well as for ampacity. On the exam, voltage drop is one of the calculation families you can count on, next to [ampacity derating](/blog/ampacity-derating-electrician-exam-nec-310-15), [conduit fill and box fill](/blog/conduit-fill-box-fill-calculations-electrician-exam) and load calculations. The good news is that it is one formula, used three ways: find the drop, find the wire size, or find the maximum length. Learn the formula once and all three question types become routine.

Free: the 20 facts Electrician exams keep testing

Top 20 most-tested facts for your exam. Delivered instantly.

The Formula and What Each Letter Means

Single-phase: VD = (2 × K × I × L) ÷ CM. Three-phase: VD = (1.732 × K × I × L) ÷ CM. K is the resistivity of the conductor in ohm-circular mils per foot. Exam questions use 12.9 for copper and 21.2 for aluminum, which come from the Chapter 9, Table 8 resistances at 75°C. If a question gives you a different K, use theirs. I is the load current in amps. Use the actual load, not the breaker size, unless the question tells you to. L is the one-way distance from the source to the load, in feet. The 2 in the single-phase formula already accounts for the current going out on one conductor and coming back on the other, so never double the length yourself. On three-phase circuits the 2 is replaced by 1.732 (the square root of 3). CM is the conductor area in circular mils from Chapter 9, Table 8: 14 AWG is 4,110, 12 AWG is 6,530, 10 AWG is 10,380, 8 AWG is 16,510, 6 AWG is 26,240 and 4 AWG is 41,740. Parallel conductors add their areas, so two 1/0 conductors per phase count as 2 × 105,600 = 211,200 cmil.

The 3% and 5% Recommendation (and Where It Is Mandatory)

The Informational Notes to 210.19(A) for branch circuits and 215.2(A) for feeders recommend a maximum of 3% drop on a branch circuit and 5% for feeder plus branch circuit combined. Informational Notes are not enforceable, so for a general branch circuit this is a design recommendation, and exam questions often test exactly that point. A few articles make voltage drop mandatory. Fire pumps (695.7) limit the drop to 15% at the controller while the motor starts and 5% at the motor while it runs at 115% of full-load current. Sensitive electronic equipment circuits under Article 647 have their own lower limits. If the question names one of those systems, look up that article instead of using 3% and 5%. When you upsize ungrounded conductors for voltage drop, 250.122(B) requires the equipment grounding conductor to be increased in proportion to the circular-mil increase. That rule is a favourite follow-up question.

Worked Example 1: Find the Drop

A 120 V, single-phase, 20 A load is 75 ft from the panel on 12 AWG copper. What is the voltage drop? VD = (2 × 12.9 × 20 × 75) ÷ 6,530 = 38,700 ÷ 6,530 ≈ 5.93 V. Percent = 5.93 ÷ 120 × 100 ≈ 4.9%. That is over the 3% branch-circuit recommendation, so the next question is usually what size would fix it. Same load on a 480 V, three-phase feeder: 65 A over 300 ft on 4 AWG copper. VD = (1.732 × 12.9 × 65 × 300) ÷ 41,740 ≈ 10.44 V, which is about 2.2% of 480 V.

Worked Example 2: Find the Wire Size

A 240 V, single-phase, 45 A load is 180 ft away. What is the smallest copper conductor that keeps the drop at or below 3%? Allowed drop = 3% × 240 V = 7.2 V. Rearranged formula: CM = (2 × K × I × L) ÷ VD = (2 × 12.9 × 45 × 180) ÷ 7.2 = 208,980 ÷ 7.2 = 29,025 cmil. 6 AWG is 26,240 cmil, which is too small, so the answer is 4 AWG (41,740 cmil). Always round up to the first size that has at least the required circular mils. Notice that 45 A alone would only need 8 AWG copper at 75°C, so here voltage drop, not ampacity, sets the size. The final wire must still meet both.

Worked Example 3: Find the Maximum Length

How far can a 120 V, 20 A load be on 12 AWG copper before the drop passes 3%? Allowed drop = 3.6 V. Solve for length: L = (VD × CM) ÷ (2 × K × I) = (3.6 × 6,530) ÷ (2 × 12.9 × 20) = 23,508 ÷ 516 ≈ 45.6 ft. Double the voltage to 240 V and the allowed drop doubles to 7.2 V, so the same wire reaches about 91 ft.

The Ohms-per-1,000-Feet Method

Some questions give you resistance instead of K, for example 12 AWG copper at about 2 ohms per 1,000 ft. Then use Ohm's law: VD = I × R, where R is the resistance of the total conductor length, out and back. For 20 A at 75 ft on 12 AWG with Table 8's 1.98 ohms per 1,000 ft: R = 150 ft × 1.98 ÷ 1,000 = 0.297 ohms, and VD = 20 × 0.297 ≈ 5.94 V. That matches the K method to within rounding, which is a good way to check yourself.

The Traps Examiners Use

Forgetting the 2 (or the 1.732). Leaving it out gives exactly half the single-phase answer, and that wrong number is almost always one of the choices. Doubling the length as well as using the 2. That gives twice the real drop. L is one-way. Using the copper K for aluminum. Aluminum drops about 64% more voltage than copper of the same size (21.2 ÷ 12.9). Mixing up volts and percent. 4.74 V on a 120 V circuit is 3.95%, not 4.74%. Read what the question asks for. Rounding the wire size down. A required 29,025 cmil is never 6 AWG. Treating 3% as a code requirement on a general branch circuit. It is a recommendation unless another article or the AHJ makes it mandatory.

How to Practise It

Write the formula at the top of your scratch paper before the exam starts, along with K = 12.9 and 21.2 and the circular mils for 14 through 4 AWG. Then drill the three question types until each takes under two minutes. Check your hand calculations with the free [voltage drop calculator](/tools/voltage-drop), size conductors with the [wire size tool](/tools/wire-size), then move on to timed sets in the [free electrician practice test](/free-electrician-practice-test) and the [Electrician study bank](/study/electrician), where every question has an AI tutor explanation. For the full study plan, see [how to pass the journeyman electrician exam](/blog/how-to-pass-journeyman-electrician-exam).

AI

Studying with VoltAI

Stuck on a Electrician question? Ask VoltAI why.

VoltAI is a built-in AI tutor that explains every practice answer in plain language — citing the actual code, protocol, or standard — and answers your follow-ups until it clicks. Most prep apps just tell you the right letter; VoltAI teaches the reasoning the exam actually tests, so you pass by understanding, not memorizing. Free to try, no account.

Try VoltAI free →