Ampacity Derating on the Electrician Exam: NEC 310.15 Correction and Adjustment Factors
How to derate conductor ampacity for the journeyman electrician exam: Table 310.16 × temperature correction × adjustment factor, then the 110.14(C) termination check. Three worked examples, the conductor-counting rules and the traps examiners use.
Problem this solves
This guide solves the next-step problem for Electrician candidates: it explains what matters, then gives you a direct way to test that knowledge with practice questions instead of guessing what to study next.
Why Derating Shows Up on Every Journeyman Exam
Table 310.16 is the most-used table in the NEC, and it comes with a fine print that most candidates skip: its ampacities assume no more than three current-carrying conductors in a raceway or cable, at an ambient temperature of 30°C (86°F). Change either condition and the conductor can no longer carry the number printed in the table. Examiners love this, because it turns a one-line lookup into a three-step calculation with a trap at every step. Expect at least one question that hands you a crowded conduit, a hot attic or a rooftop run and asks what the wire can actually carry, or what size you need. The method is the same every time, so it is some of the most reliable points on the test once you have drilled it. You can check every example below with our free [ampacity derating calculator](/tools/ampacity-derating).
Try it now — no account, no download
Practice Electrician questions free
Answer 5 Electrician practice questions with instant explanations before you keep reading.
Electrician · Question 1 of 5
What is the minimum size copper grounding electrode conductor required for a service supplied by 3/0 AWG copper service-entrance conductors?
Pick an answer to see the explanation + an instant AI breakdown.
The Formula: Base × Correction × Adjustment, Then the Termination Check
Allowable ampacity = Table 310.16 ampacity × temperature correction factor × adjustment factor, and the answer can never be more than the ampacity in the column your terminations are rated for. Step 1 — base ampacity. Look up the conductor in Table 310.16 using its insulation's own column. THHN and THWN-2 are 90°C, so 12 AWG copper starts at 30 A, 10 AWG at 40 A, 8 AWG at 55 A. Step 2 — temperature correction. Table 310.15(B)(1)(1) (2023 NEC numbering) gives a factor for the ambient temperature. For the 90°C column: 31–35°C is 0.96, 36–40°C is 0.91, 41–45°C is 0.87, 46–50°C is 0.82. Below 30°C the factor is above 1.00, but exam questions almost always go hotter. Step 3 — adjustment factor. Table 310.15(C)(1) applies when more than three current-carrying conductors share a raceway or cable: 4–6 conductors 80%, 7–9 conductors 70%, 10–20 conductors 50%, 21–30 conductors 45%, 31–40 conductors 40%, 41 and above 35%. Step 4 — termination check. NEC 110.14(C) limits the final ampacity to the column of the lowest-rated termination: 60°C by default for circuits rated 100 A or less or 14 through 1 AWG conductors, 75°C above 100 A or where the equipment is listed for it. Compare your derated number with the Table 310.16 value in that column and use whichever is lower.
Free: the 20 facts Electrician exams keep testing
Top 20 most-tested facts for your exam. Delivered instantly.
Worked Example 1: The Crowded Conduit
Nine 12 AWG THHN copper current-carrying conductors run in one conduit through a space at 40°C. Terminations are 60°C. What is the allowable ampacity? Base (90°C column): 30 A. Correction at 40°C: 0.91. Adjustment for 7–9 conductors: 0.70. 30 × 0.91 × 0.70 = 19.11 A. Termination check: 12 AWG in the 60°C column is 20 A. 19.11 A is lower, so the answer is 19.11 A. Notice what happened: the 90°C insulation absorbed most of the derating. Had you started from the 60°C column, you would have computed 20 × 0.82 × 0.70 = 11.48 A, a wrong answer that is very likely sitting among the choices.
Worked Example 2: When the Terminations Win
Four 6 AWG THHN copper current-carrying conductors in one raceway at 30°C, 60°C terminations. Base: 75 A. Correction: 1.00. Adjustment for 4–6 conductors: 0.80. Derated: 60 A. Termination limit for 6 AWG at 60°C: 55 A. Answer: 55 A. This is the second half of the trap. Candidates who stop at the derated number pick 60 A. The question writer knows 90°C wire often derates to a value that is still above the termination column, and the termination is what decides. Always finish with the termination check, even when the derating looks like the whole question.
Worked Example 3: Sizing the Wire for a Load
The reverse question: a 42 A noncontinuous load, four current-carrying THHN copper conductors in the raceway, 38°C ambient, 60°C terminations. What minimum conductor size is required? Try 8 AWG: 55 × 0.91 × 0.80 = 40.04 A. Too small. Try 6 AWG: 75 × 0.91 × 0.80 = 54.6 A, and the 60°C limit for 6 AWG is 55 A, so 54.6 A is allowable. Answer: 6 AWG. If the load is continuous, add one more rule. Under 210.19(A)(1) the conductor must be the larger of 125% of the continuous load before any correction or adjustment, or 100% of the load after correction and adjustment. You do not stack the 125% on top of the derating — you check both and take the larger requirement.
What Counts as a Current-Carrying Conductor
Counting conductors is where most derating questions are really won or lost. Every ungrounded (hot) conductor counts. A neutral that carries only the unbalanced current of other conductors in the same circuit does not count (310.15(E)), so a 3-wire multiwire branch circuit is two current-carrying conductors, not three. The exception that gets tested: on a 3-phase, 4-wire wye system where the major portion of the load is nonlinear (electronic ballasts, computers, LED drivers), the neutral carries harmonic currents and must be counted. Equipment grounding conductors and bonding jumpers never count (310.15(F)). Worked count: a conduit holds two 3-phase, 4-wire circuits feeding linear loads plus one equipment grounding conductor. Hots: 6. Neutrals: not counted. Ground: not counted. Six conductors, 80%. Change the loads to mostly nonlinear and you have eight, so 70%.
The Four Exceptions Examiners Like
Short nipples: adjustment factors do not apply to a raceway 24 inches or shorter. Rooftops: under 310.15(B)(2), a raceway or cable in direct sunlight less than 7/8 inch (23 mm) above the roof gets 33°C (60°F) added to the outdoor ambient before you pick the correction factor; Type XHHW-2 is exempt. A 32°C rooftop run therefore uses a 65°C ambient, and 90°C wire takes a 0.65 factor. Small conductors: 240.4(D) caps the overcurrent device for 14, 12 and 10 AWG copper at 15, 20 and 30 A, but it does not lower the ampacity. Four 12 AWG THHN at 30°C derate to 30 × 0.80 = 24 A, so a 20 A breaker still works as long as the load fits. And edition numbering: the 2023 NEC moved the tables to 310.15(B)(1)(1) and 310.15(C)(1); the 2017 and earlier editions used 310.15(B)(2)(a) and 310.15(B)(3)(a). Tab whichever edition your state adopted.
A 10-Minute Drill to Lock It In
Put three tabs in your code book: Table 310.16, the correction table and the adjustment table. Then run this drill until it takes you under two minutes per question: write the base, the two factors and the termination limit on four lines, multiply, and circle the lower of the last two numbers. Work the examples above by hand, then check yourself with the [ampacity derating calculator](/tools/ampacity-derating), which shows the same four steps. When the method is automatic, move on to timed sets in the free [electrician practice test](/free-electrician-practice-test) and the [Conductors & Ampacity questions](/study/electrician). For the rest of the calculation family, see [conduit fill and box fill](/blog/conduit-fill-box-fill-calculations-electrician-exam), [voltage drop](/blog/voltage-drop-calculation-electrician-exam) and the full [how to pass the journeyman electrician exam](/blog/how-to-pass-journeyman-electrician-exam) guide.
Free Electrician Tools
Studying with VoltAI
Stuck on a Electrician question? Ask VoltAI why.
VoltAI is a built-in AI tutor that explains every practice answer in plain language — citing the actual code, protocol, or standard — and answers your follow-ups until it clicks. Most prep apps just tell you the right letter; VoltAI teaches the reasoning the exam actually tests, so you pass by understanding, not memorizing. Free to try, no account.
Try VoltAI free →Your next best step
Turn this guide into practice
Use the article to understand the topic, then do a short web practice session to find your weak spots. Paid web access is optional after the free preview.