Ampacity Derating Calculator (NEC 310.15)
Enter the wire, the ambient temperature and how many current-carrying conductors share the raceway. The calculator applies the temperature correction and adjustment factors, then checks the termination limit — and shows every step so you can do it by hand on exam day.
86°F. Table basis is 30°C (86°F).
Don't count grounding conductors or a neutral that carries only unbalanced current.
Allowable ampacity
20A
- 1. Table 310.16, 90°C column: 30 A
- 2. Temperature correction at 30°C: × 1.00
- 3. Adjustment for 6 conductors: × 0.80
- 4. Derated: 24 A
- 5. Termination limit (60°C column): 20 A → use the lower value
The terminations, not the derating, set the limit here. Small-conductor rule (240.4(D)): overcurrent protection for 12 AWG copper is capped at 20 A.
Copper only, NEC 2023 numbering (Tables 310.16, 310.15(B)(1)(1), 310.15(C)(1)). Check the edition your state adopted. Study aid, not a design tool.
Try it now — no account, no download
Practice conductor & ampacity questions
Real NEC exam-style questions, each with an instant AI explanation.
Electrician / NEC · Question 1 of 5
What is the allowable ampacity of a 10 AWG THHN copper conductor at 30°C ambient temperature?
Pick an answer to see the explanation + an instant AI breakdown.
Ampacity derating in four steps
Table 310.16 assumes no more than three current-carrying conductors at a 30°C (86°F) ambient. Change either condition and the conductor can no longer carry its table value. The exam tests this every time: a hot attic, a rooftop run or a conduit full of circuits, and a question asking what the wire can actually carry.
Worked example: nine 12 AWG THHN copper conductors in one conduit through a 40°C space, 60°C terminations. Base ampacity (90°C column) is 30 A. Temperature correction at 40°C is 0.91. Seven to nine conductors take a 70% adjustment. 30 × 0.91 × 0.70 = 19.11 A. The 60°C column limit for 12 AWG is 20 A, so 19.11 A is the allowable ampacity.
Going the other way, sizing a conductor for a 42 A load with four current-carrying THHN conductors at 38°C: 8 AWG gives 55 × 0.91 × 0.80 = 40.04 A (too small), 6 AWG gives 75 × 0.91 × 0.80 = 54.6 A, under its 55 A 60°C limit. Answer: 6 AWG. The full method, with the traps examiners use, is in our ampacity derating exam guide.
NEC Table 310.15(C)(1) adjustment factors
| Current-carrying conductors | Percent of table ampacity |
|---|---|
| 4–6 | 80% |
| 7–9 | 70% |
| 10–20 | 50% |
| 21–30 | 45% |
| 31–40 | 40% |
| 41 and above | 35% |
NEC 2023 numbering. Earlier editions placed these tables at 310.15(B)(2)(a) and 310.15(B)(3)(a).
Frequently Asked Questions
How do you calculate ampacity derating?
Start from the conductor's insulation column in NEC Table 310.16 (the 90°C column for THHN/THWN-2). Multiply by the ambient temperature correction factor from Table 310.15(B)(1)(1) and by the adjustment factor from Table 310.15(C)(1) for more than three current-carrying conductors. Then compare the result to the ampacity in the column your terminations are rated for (usually 60°C or 75°C, per 110.14(C)) and use the lower number. Example: nine 12 AWG THHN in one conduit at 40°C = 30 A × 0.70 × 0.91 = 19.11 A.
What are the NEC adjustment factors for more than three current-carrying conductors?
Table 310.15(C)(1): 4–6 conductors 80%, 7–9 conductors 70%, 10–20 conductors 50%, 21–30 conductors 45%, 31–40 conductors 40%, and 41 or more 35%. The factors do not apply to a raceway 24 inches long or shorter.
Which conductors count as current-carrying?
Every ungrounded (hot) conductor counts. A neutral that carries only the unbalanced current of the same circuit does not count (310.15(E)), but a neutral on a 3-phase, 4-wire wye circuit where the major portion of the load is nonlinear does count. Equipment grounding and bonding conductors never count (310.15(F)).
Why do I derate from the 90°C column but end up at 60°C or 75°C?
310.15(B) lets you apply correction and adjustment factors to the insulation's own ampacity, so 90°C wire gives you more room before derating bites. But 110.14(C) says the final ampacity can never exceed the column the terminations are rated for: 60°C by default for circuits of 100 A or less or 14–1 AWG conductors, and 75°C above 100 A or where the equipment is listed for it. Use whichever is lower.
What is the rooftop temperature adder?
Under 310.15(B)(2), raceways or cables exposed to direct sunlight on or above a rooftop and installed less than 7/8 inch (23 mm) above the roof get 33°C (60°F) added to the outdoor ambient before you pick the correction factor. Type XHHW-2 conductors are exempt.
Does the 240.4(D) small-conductor rule change the ampacity?
No. 240.4(D) caps the overcurrent device for 14, 12 and 10 AWG copper at 15, 20 and 30 amps. Derating can give 12 AWG THHN an ampacity above 20 A (for example 24 A with four conductors at 30°C), which is why exam questions often let you keep a 20 A breaker on derated 12 AWG — the ampacity must still cover the load.