Dwelling Unit Load Calculator
Work a house service calculation the way the journeyman electrician exam asks it: NEC Article 220 standard method or the 220.82 optional method, every demand factor on its own line, then the service size and the 310.12 service conductors. The example loaded below is the one from our step-by-step dwelling load guide.
Method
Outside dimensions; no open porches or garages
20 A kitchen/dining, minimum 2
Minimum 1
0 if gas or none
One range; 0 if gas or none
Calculated load (standard method)
35,200 VA → 146.7 A at 240 V
Minimum service: 150 A (next standard size, 240.6(A))
Service conductors at 83% (310.12): ≥ 124.5 A → 1 AWG copper or 2/0 AWG aluminum (Table 310.16, 75 °C)
Show the work
- General lighting + small-appliance + laundry (after demand): 5,625 VA2,000 sq ft × 3 VA = 6,000 VA + 3 × 1,500 VA = 10,500 VA → first 3,000 at 100%, 7,500 at 35%
- Fastened-in-place appliances: 6,075 VA4 appliances, 8,100 VA × 75% (four or more, 220.53)
- Clothes dryer: 5,500 VALarger of 5,000 VA or 5,500 VA nameplate (220.54)
- Household range: 8,000 VATable 220.55 Column C, one range not over 12 kW = 8 kW
- Space heating (larger than A/C): 10,000 VAHeat 10,000 VA vs A/C 5,000 VA — count only the larger (220.60)
- Total 35,200 VA ÷ 240 V = 146.7 A → 150 A service
What this tool covers
One-family dwelling, 120/240 V single-phase, one household range, NEC 2020/2023 values (3 VA per sq ft). Not included: motors (430.24's extra 25% of the largest motor), heat-pump supplemental-heat options of 220.82(C), multiple cooking appliances, neutral load (220.61) and multifamily (220.84). The 2026 NEC moves these rules to Article 120 and lowers the dwelling lighting load, so check your exam's edition.
For exam practice and estimation only — not a substitute for engineered design, manufacturer data, current codes, or a licensed professional's judgment. Verify all values before relying on them.
Teaching this? Use the nec dwelling load calculator free in class
Apprenticeship instructors and trade schools can link students to this calculator at no cost. No sign-up for students. Paste the link into your course page, LMS or a forum post.
Try it now — no account, no download
Practice 5 Electrician / NEC exam questions
Real questions — each with an instant AI explanation.
Electrician / NEC · Question 1 of 5
What is the minimum size copper grounding electrode conductor required for a service supplied by 3/0 AWG copper service-entrance conductors?
Pick an answer to see the explanation + an instant AI breakdown.
The Standard Method in Five Lines
- Lighting and required circuits: sq ft × 3 VA + 1,500 VA per small-appliance circuit (at least two) + 1,500 VA laundry.
- Demand factors: first 3,000 VA at 100%, the next 117,000 VA at 35%, the rest at 25%. Apply 35% only to the part over 3,000 VA.
- Fastened-in-place appliances: 75% of the total when there are four or more (220.53). The range, dryer, heat and A/C are not in this group.
- Dryer and range: dryer at 5,000 VA or nameplate, whichever is larger (220.54); range from Table 220.55.
- Heat or A/C, not both (220.60). Total ÷ 240 V, round up to the next standard size (240.6(A)).
Related: conduit fill calculator · ampacity derating calculator · optional method guide · free electrician practice test
Frequently Asked Questions
How do you calculate a dwelling unit service load?
With the NEC standard method: general lighting at 3 VA per square foot plus 1,500 VA for each small-appliance circuit (at least two) and the laundry circuit; apply the demand factors (first 3,000 VA at 100%, the next 117,000 VA at 35%, the rest at 25%); add fastened-in-place appliances (75% if four or more), the dryer (larger of 5,000 VA or nameplate), the range from Table 220.55 and the larger of heat or A/C. Divide by 240 V and round up to the next standard service size. A 2,000 sq ft house with a 12 kW range, 5.5 kW dryer, four appliances and 10 kW of heat is 35,200 VA, 146.7 A, a 150 A service.
What is the optional method for a dwelling load calculation?
NEC 220.82, for a single dwelling with a service of 100 A or more. Add 3 VA per square foot, 1,500 VA per small-appliance and laundry circuit and the nameplate ratings of the fastened appliances, range and dryer. Take the first 10 kVA at 100% and the rest at 40%, then add the largest of the air conditioning at 100% or electric space heat at 65% (fewer than four separately controlled units) or 40% (four or more). The same house works out to 26,940 VA, 112.3 A, a 125 A service.
How much does an electric range count for in a load calculation?
Use Table 220.55. One range over 8¾ kW and not over 12 kW counts 8 kW (Column C). Over 12 kW, Note 1 adds 5% to the 8 kW for each kW or major fraction over 12: a 14 kW range counts 8.8 kW. From 1¾ to 8¾ kW, Note 3 allows Column B, 80% of the nameplate for one appliance.
Do you add both the heating and the air conditioning?
No. Heat and A/C are noncoincident loads, so NEC 220.60 lets you count only the larger. Adding both is one of the most common wrong answers on the exam.
What size service conductors does a 150 A dwelling service need?
For a 120/240 V dwelling service of 100 A to 400 A, 310.12 lets the service conductors be sized at 83% of the service rating: 150 A × 0.83 = 124.5 A, so 1 AWG copper (130 A) or 2/0 aluminum (135 A) from the 75 °C column of Table 310.16.