Motor Circuit Calculator

One motor, four different numbers: the conductors, the overload, the breaker or fuse and the disconnect, each from its own NEC Article 430 rule. Pick the horsepower and voltage and the calculator shows every step, or switch to feeder mode for several motors on one feeder. The example loaded below is the one from our Article 430 motor calculations guide.

Phase

Conductors 8 AWG copper, overload 40 amps, branch protection 90 amps.

Conductors

8 AWG Cu

min 42.5 A · 6 AWG Al

Overload

40 A

125% of nameplate

Branch protection

90 A

max, 250% of FLC

Show the work

  1. Full-load current (25 hp, 460 V, 3φ): 34 ANEC Table 430.250; 430.6(A)(1)
  2. Branch-circuit conductors: 125% of FLC: 34 × 1.25 = 42.5 A → 8 AWG Cu (50 A) or 6 AWG Al (50 A)NEC 430.22; Table 310.16 (75 °C)
  3. Overload: 125% of nameplate FLA: 32 × 1.25 = 40 A maximumNEC 430.32(A)(1)
  4. Short-circuit & ground-fault: Inverse-time breaker (250%): 34 × 2.5 = 85 A → next standard size up: 90 ANEC Table 430.52; 430.52(C)(1) Exc. 1; 240.6(A)
  5. Disconnecting means: at least 115% of FLC: 34 × 1.15 = 39.1 ANEC 430.110(A)

What this tool covers

General-purpose, continuous-duty AC induction motors using the NEC 2020/2023 Article 430 tables. Conductors use the 75 °C column of Table 310.16 with no temperature correction or bundling (see the ampacity derating calculator for that). Table 430.52 percentages are for motors other than Design B energy-efficient premium, whose instantaneous-trip limit is 1,100%. The exceptions that allow a larger device when the motor will not start (430.52(C)(1) Exc. 2, 430.32(C)) are not applied.

For exam practice and estimation only — not a substitute for engineered design, manufacturer data, current codes, or a licensed professional's judgment. Verify all values before relying on them.

Teaching this? Use the nec motor circuit calculator free in class

Apprenticeship instructors and trade schools can link students to this calculator at no cost. No sign-up for students. Paste the link into your course page, LMS or a forum post.

Try it now — no account, no download

Practice 5 Electrician / NEC exam questions

Real questions — each with an instant AI explanation.

Electrician / NEC · Question 1 of 5

What is the minimum size copper grounding electrode conductor required for a service supplied by 3/0 AWG copper service-entrance conductors?

Pick an answer to see the explanation + an instant AI breakdown.

One Motor, Four Rules

  1. Start from the table, not the nameplate: Table 430.250 (3φ) or 430.248 (1φ) by horsepower and voltage (430.6(A)(1)).
  2. Conductors: 125% of the table FLC, 75 °C column of Table 310.16. No next-size-up for conductors (430.22).
  3. Overload: the one step that uses the nameplate FLA. 125% with a 1.15+ service factor or a 40 °C rise, otherwise 115% (430.32).
  4. Breaker or fuse: Table 430.52 percentage of the table FLC, then the next standard size UP is allowed (430.52(C)(1) Exc. 1).
  5. Feeder: 125% of the largest FLC + the rest for conductors (430.24); largest branch device + the other FLCs for protection, rounded DOWN (430.62(A)).

Related: motor feeder calculation guide · ampacity derating calculator · voltage drop calculator · free electrician practice test

Frequently Asked Questions

How do you size a motor circuit on the electrician exam?

Look up the full-load current in Table 430.250 (three-phase) or 430.248 (single-phase) by horsepower and voltage, then size four things from it. Conductors: 125% of the table FLC (430.22). Overload: 115% or 125% of the NAMEPLATE amps (430.32). Breaker or fuse: the Table 430.52 percentage of the table FLC, rounded up to the next standard size. Disconnect: at least 115% of the FLC (430.110). A 25 hp, 460 V motor is 34 A from the table: 42.5 A conductors (8 AWG copper), a 40 A overload from a 32 A nameplate with a 1.15 service factor, and 85 A for an inverse-time breaker, which rounds up to 90 A.

Do you use the nameplate or the table current for motors?

The table. NEC 430.6(A)(1) requires the Table 430.247–430.250 full-load current for conductors, short-circuit and ground-fault protection, disconnects and feeders. The nameplate FLA is used for the overload only (430.32). Exams give you both numbers because the nameplate is the tempting wrong one.

What breaker size does a motor need?

Multiply the table FLC by the Table 430.52 percentage for the device: 250% for an inverse-time breaker, 175% for a dual-element (time-delay) fuse, 300% for a non-time-delay fuse, 800% for an instantaneous-trip breaker. If the result is not a standard size from 240.6(A), 430.52(C)(1) Exception No. 1 lets you go to the next higher standard size: 34 A × 2.5 = 85 A becomes a 90 A breaker.

How do you size a feeder for several motors?

Conductors (430.24): 125% of the largest motor's FLC plus 100% of the others. Protection (430.62(A)): the largest branch-circuit breaker or fuse plus the FLCs of the other motors, and the result is a maximum, so you round DOWN to a standard size. Three 460 V motors of 25, 10 and 5 hp (34, 14 and 7.6 A) need 34 × 1.25 + 14 + 7.6 = 64.1 A conductors, and 90 A + 14 + 7.6 = 111.6 A protection, which rounds down to 110 A.

When is the motor overload 125% instead of 115%?

Under 430.32(A)(1), 125% of the nameplate FLA applies when the motor's marked service factor is 1.15 or more, or its marked temperature rise is 40 °C or less. Every other continuous-duty motor over 1 hp gets 115%.