Motor Feeder Calculation on the Electrician Exam: NEC 430.24 and 430.62 Step by Step

How to size a feeder for several motors on the journeyman electrician exam: 125% of the largest FLC plus the rest for conductors (430.24), the largest branch breaker plus the other FLCs for protection (430.62), rounded down — with a worked three-motor example.

Problem this solves

This guide solves the next-step problem for Electrician candidates: it explains what matters, then gives you a direct way to test that knowledge with practice questions instead of guessing what to study next.

TL;DR

To size a motor feeder on the journeyman electrician exam, look up every motor's full-load current (FLC) in Table 430.250 or 430.248, never the nameplate. Feeder conductors (NEC 430.24): 125% of the largest motor's FLC plus 100% of every other motor's FLC. Feeder protection (NEC 430.62(A)): the rating of the largest branch-circuit breaker or fuse plus the FLCs of the other motors, and because that is a maximum you round DOWN to a standard size. Three 460 V motors of 25, 10 and 5 hp (34, 14 and 7.6 A) need 64.1 A conductors (6 AWG copper) and a feeder breaker no larger than 111.6 A, so 110 A. Check it in our free motor circuit calculator, which has a feeder mode.

Try it now — no account, no download

Practice Electrician questions free

Answer 5 Electrician practice questions with instant explanations before you keep reading.

Electrician · Question 1 of 5

What is the minimum size copper grounding electrode conductor required for a service supplied by 3/0 AWG copper service-entrance conductors?

Pick an answer to see the explanation + an instant AI breakdown.

Two Rules, Two Rounding Directions

A motor feeder question is really two calculations that start from the same numbers and then go opposite ways. The conductor rule adds a 25% margin to one motor only, the largest, because a group of motors rarely runs every machine at full load while the biggest one is also starting. The protection rule starts from the biggest branch-circuit device, which is already oversized to ride through starting current, and adds the running current of everything else. The exam tests the rounding as hard as the arithmetic. Conductors take the smallest size whose ampacity meets the calculated value. The branch-circuit breaker for each motor may go UP to the next standard size (430.52(C)(1) Exception No. 1). The feeder breaker may not: 430.62(A) says the rating shall not be greater than the calculated value, so you go DOWN. Candidates who have just practiced a branch-circuit question carry the round-up habit straight into the feeder and pick the distractor.

Free: the 20 facts Electrician exams keep testing

Top 20 most-tested facts for your exam. Delivered instantly.

Step 1: Find Each Motor's FLC

430.6(A)(1) applies to feeders exactly as it does to branch circuits: use the table current. Table 430.250 covers three-phase induction motors and Table 430.248 single-phase. Look up each motor by horsepower and the system voltage, write the three or four numbers in a column and circle the largest. The largest is the motor with the largest FLC, not necessarily the largest horsepower. On a 208Y/120 V feeder a 3 hp, 115 V single-phase motor (34 A) draws more than a 7-1/2 hp, 208 V three-phase motor (24.2 A), and that is exactly the kind of setup a test writer uses to see whether you compare amperes or horsepower. Ignore the nameplate FLA for every step in this article. It sizes the overload and nothing else.

Step 2: Feeder Conductors (430.24)

Multiply the largest FLC by 1.25 and add the FLC of every other motor at 100%. Then pick a conductor from the 75 °C column of Table 310.16 (termination limits under 110.14(C) usually put you there) whose ampacity is at least that number. The classic wrong answer applies 125% to every motor. With 34, 14 and 7.6 A that gives 69.5 A and a 4 AWG conductor, one size too large, and it will be one of the four options. If the feeder also serves other equipment, 430.24 adds those loads too: 125% of any continuous non-motor load and 100% of any noncontinuous non-motor load. Most exam questions keep the feeder motor-only, so read the stem for a heater or lighting panel before you finish.

Step 3: Size Each Branch-Circuit Device

You cannot do 430.62 until you know the largest branch-circuit short-circuit and ground-fault device, so work each motor through Table 430.52: 250% of FLC for an inverse-time breaker, 175% for a dual-element fuse, 300% for a non-time-delay fuse, 800% for an instantaneous-trip breaker. Then apply the next-size-up exception where the result is not a standard 240.6(A) rating. For the example: 34 × 2.5 = 85 A, which becomes 90 A; 14 × 2.5 = 35 A, already standard; 7.6 × 2.5 = 19 A, which becomes 20 A. If two motors end up with the same largest device, 430.62(A) says to treat one of them as the largest. Our Article 430 motor calculations guide walks the single-motor version of this step in detail.

Step 4: Feeder Protection (430.62(A))

Take the largest branch-circuit device rating, 90 A here, and add the FLCs of all the other motors, not their breakers: 90 + 14 + 7.6 = 111.6 A. That is the maximum the feeder device may be. 111.6 A is not a standard size, so drop to the next standard rating below it, 110 A. Two traps hide in this step. The first is adding all the branch breakers together (90 + 35 + 20 = 145 A), which double-counts starting current that never happens on every motor at once. The second is rounding up to 125 A because that is what you did one step earlier. If 110 A is not among the options, the answer is still the largest standard size that does not exceed 111.6 A.

The Worked Example on One Page

Feeder to three 460 V, three-phase motors with inverse-time breakers: 25 hp, 10 hp and 5 hp. FLCs from Table 430.250: 34 A, 14 A, 7.6 A, with 34 A the largest. Conductors: 34 × 1.25 = 42.5 A, plus 14 and 7.6, equals 64.1 A, so 6 AWG copper at 65 A in the 75 °C column, or 4 AWG aluminum at 65 A. Branch breakers: 90 A, 35 A, 20 A. Feeder breaker: 90 + 14 + 7.6 = 111.6 A, round down, 110 A. Notice how tight the conductor is: 64.1 A against a 65 A rating. An exam writer who wants to test the 125%-on-everything mistake picks numbers like these on purpose, because the wrong method pushes the answer one size up. Run your own combinations in the motor circuit calculator and compare against the ampacity derating calculator if the question adds ambient temperature or bundling.

Practice Plan

Feeder questions are short once the order is automatic, so drill the order rather than the numbers. For every practice question, write four lines before you look at the options: the FLC column with the largest circled, the conductor line, the branch device for the largest motor, and the feeder device with an arrow pointing down. That takes under a minute and catches every trap in this article. Tab Tables 430.250, 430.248, 430.52 and 310.16 so the lookups are instant on an open-book exam. Confirm which NEC edition your state tests; these section numbers are the same in the 2020 and 2023 codes. Then work mixed sets at our free electrician practice test, or ask the VoltExam AI tutor why a choice you picked was wrong.

AI

Studying with VoltAI

Stuck on a Electrician question? Ask VoltAI why.

VoltAI is a built-in AI tutor that explains every practice answer in plain language — citing the actual code, protocol, or standard — and answers your follow-ups until it clicks. Most prep apps just tell you the right letter; VoltAI teaches the reasoning the exam actually tests, so you pass by understanding, not memorizing. Free to try, no account.

Try VoltAI free →