Free Tool — Backflow Tester
Backflow PSID Calculator
Enter field test readings for any backflow prevention assembly — DC, RP, PVB, or SVB — and get instant pass/fail results per USC and AWWA M14 differential pressure criteria.
Assembly Type
Two independently acting check valves. Used for low (non-health) hazard cross-connections.
High hose on TC2, low hose on TC3, No. 2 shutoff closed — differential across first check valve
High hose on TC3, low hose on TC4 — differential across second check valve
Pass/Fail Criteria — All Assembly Types
| Assembly | Check 1 | Relief / Air Inlet | Check 2 |
|---|---|---|---|
| DC / DCVA | ≥ 1.0 psi | — | ≥ 1.0 psi |
| RP / RPBA | ≥ 5.0 psi | ≥ 2.0 psi & < Check 1 | Tight (≥ 1.0 psi common) |
| PVB | ≥ 1.0 psi | Air inlet opens ≥ 1.0 psi | — |
| SVB | ≥ 1.0 psi | Air inlet opens ≥ 1.0 psi | — |
Source: USC Foundation for Cross-Connection Control, AWWA M14. Verify against your state or local authority having jurisdiction (AHJ) requirements.
For exam practice and estimation only — not a substitute for engineered design, manufacturer data, current codes, or a licensed professional's judgment. Verify all values before relying on them.
Try it now — no account, no download
Practice 5 Backflow Tester exam questions
Real questions — each with an instant AI explanation.
Backflow Tester · Question 1 of 5
When performing a Double Check Valve assembly test, what is the first step in the preliminary procedure?
Pick an answer to see the explanation + an instant AI breakdown.
Backflow PSID Testing — What You Need to Know
Differential pressure (PSID) is the core measurement in backflow prevention testing. A properly functioning backflow assembly maintains positive pressure differential across its check valves — meaning the inlet side always holds more pressure than the outlet side, preventing contaminated water from flowing back into the potable supply. A differential pressure gauge (test kit) directly measures this pressure difference across each component during a field test.
The four main assembly types each have distinct test procedures and minimum PSID thresholds. Double Check Valve (DC) assemblies are the simplest — both checks must hold at least 1.0 psi. Reduced Pressure Zone (RP) assemblies are more complex: the No. 1 check must hold at least 5.0 psi, the relief valve must open at 2.0 psi or more (below the Check 1 reading), and the No. 2 check must be tight (many local procedures also record ≥ 1.0 psi). Pressure Vacuum Breakers (PVB) and Spill-Resistant Vacuum Breakers (SVB) protect only against back-siphonage and use an air inlet mechanism — both the air inlet and poppet must test at ≥ 1.0 psi.
For backflow certification exam prep, PSID calculation questions are among the most common. Know the thresholds for each assembly type cold, understand when an assembly fails (and why), and be familiar with the repair and retest requirements that follow a failed test. The certification exam also tests your knowledge of which assembly type is appropriate for different hazard levels and installation conditions.
Backflow Assembly Types — When to Use Each
Per USC Foundation for Cross-Connection Control and AWWA M14. Verify against your state or local AHJ requirements.
| Assembly | Hazard Level | Protection Type | Min. PSID |
|---|---|---|---|
| DC / DCVA | Low (non-health) | Backpressure + back-siphonage | 1.0 psi each check |
| RP / RPBA | High (health hazard) | Backpressure + back-siphonage | Check 1 ≥ 5.0, relief ≥ 2.0, Check 2 tight |
| PVB | High or low (backsiphonage only) | Back-siphonage only | Check ≥ 1.0, air inlet opens ≥ 1.0 |
| SVB | High or low (backsiphonage only; indoor) | Back-siphonage only | Check ≥ 1.0, air inlet opens ≥ 1.0 |
Note: Continuously pressurized assemblies (DC, RP) may be used in both intermittent and continuous service. PVBs and SVBs may also stay under continuous pressure, but give backsiphonage protection only and must sit at least 12 in. above the highest downstream outlet. AVBs cannot stay under continuous pressure.
Frequently Asked Questions
What does PSID mean in backflow testing?
PSID stands for Pounds per Square Inch Differential — the pressure difference measured across a check valve or assembly component during a field test. A differential pressure gauge (backflow test kit) connects to the test cocks on the assembly and measures the PSID across each component. This reading is compared to the minimum threshold to determine a pass or fail.
What PSID is needed to pass a Double Check Valve (DC) assembly?
A Double Check Valve assembly passes when both check valves hold a differential pressure of at least 1.0 psi. If either check 1 or check 2 reads below 1.0 psi, the assembly fails and requires repair or replacement before being returned to service.
What are the RP assembly pass criteria?
A Reduced Pressure Zone (RP/RPBA) assembly passes when: (1) No. 1 check holds ≥ 5.0 psi differential, (2) the relief valve opens at a differential ≥ 2.0 psi, and the No. 1 check reading is higher than that relief opening point, and (3) the No. 2 check is tight against backpressure (USC 10th edition: closed tight; many local procedures also record ≥ 1.0 psi). If the relief opens below 2.0 psi, or Check 1 is under 5.0 psi, the assembly fails.
How do I test a PVB assembly in the field?
A PVB has two tests. Check valve: with both shutoffs closed, measure the differential across the check (test cock #1 to test cock #2) — it must hold ≥ 1.0 psi. Air inlet: bleed pressure off the body slowly and note the reading when the air inlet poppet opens — it must open at ≥ 1.0 psi and open fully. The order of the two tests varies by procedure, so follow your local one. PVBs protect against backsiphonage only and must be installed at least 12 in. above the highest downstream outlet.
What is the difference between a PVB and SVB?
A Pressure Vacuum Breaker (PVB) vents water to atmosphere when the air inlet opens, which can cause spilling indoors. A Spill-Resistant Vacuum Breaker (SVB) uses a design that prevents water from spilling during the air inlet opening — making it suitable for indoor installations. Both use the same pass/fail PSID criteria: air inlet ≥ 1.0 psi and poppet/check ≥ 1.0 psi. Both PVBs and SVBs can stay under continuous pressure; they must not be used where backpressure is possible. The device that cannot stay under continuous pressure is the atmospheric vacuum breaker (AVB).
What happens if an assembly fails the PSID test?
A failed assembly must be taken out of service, repaired or replaced, and retested before it can be returned to service. The tester completes a failed test report which is typically submitted to the local water purveyor or authority having jurisdiction (AHJ). Repair must be performed by a licensed plumber or backflow tester (depending on jurisdiction). After repair, a passing retest report must be filed within the AHJ's required timeframe.
Also try: Pipe DFU Calculator
Drainage fixture units per IPC 2021 Table 710.1 — minimum horizontal drain pipe size
Want to test this on exam questions? Start Backflow Tester Prep web practice →